- #01Plan and document coordination
Obvious clerical, title-block, sheet-index, permit-description, or cross-sheet inconsistencies visible in the submitted documents. A Courtesy Comment on these items does not cause FCC to fail or return the plan set unless the same condition also creates a building-code compliance issue within FCC's review scope.
FBC-B 107.2.1 - #02Zoning and site coordination
Apparent setback, lot-coverage, use, or site-dimension conflicts visible in the submitted plans that could cause the plans to fail Planning and Zoning review. Planning and Zoning makes the zoning and lot-compliance determination. The absence of a Courtesy Comment is not approval of those separate requirements.
- #03Floodplain coordination
Apparent inconsistencies or missing coordination in flood-zone, design-flood-elevation, finished-floor, or flood-opening information shown on the plans that could cause the plans to fail floodplain review. The floodplain administrator makes the determination. The absence of a Courtesy Comment is not approval of those separate requirements.
- #04Fire-authority coordination
Apparent separately reviewed fire alarm, sprinkler, hood-suppression, smoke-control, or similar coordination issues visible on the plans that could cause the plans to fail fire review. The fire marshal makes the determination. The absence of a Courtesy Comment is not approval of those separate requirements.
Single Family Generator Install
Install a permanently mounted standby generator and transfer equipment. New fuel piping requires separate gas inspection scope.
Last updated: Sep 29, 2026
Section 1
Required Documents
Submit these with your initial project package.
Always required
- Equipment SpecificationsManufacturer specifications for the generator including capacity, fuel type, and output rating
Conditional
- Electrical Load CalculationsElectrical load calculations showing generator capacity relative to the loads it will serveWhenNeeded when an automatic transfer switch serves the whole panel (NEC 702.4(B)(2)). A manual transfer switch or load management changes what is needed; our examiner confirms.
- Site PlanSite plan showing generator placement, clearances, and fuel supply routingWhenGenerator location and clearances; a marked survey or sketch counts. Not needed to start review.
Courtesy screen
Courtesy screen on every plan review
Every plan FCC reviews receives a limited courtesy screen for the items below when they are reasonably visible in the submitted documents. If we see an apparent issue that could cause the plans to fail review by another agency, we will identify it as a Courtesy Comment. Courtesy Comments alone do not cause FCC to fail or return the plan set unless the same condition also creates a building-code compliance issue within FCC's review scope. The responsible agency makes the final determination—for example, Planning and Zoning for setbacks, lot coverage, use, and other lot-compliance matters. The absence of a Courtesy Comment is not approval of those separate requirements.
Section 2
Approval criteria for this project type
These are the building-code criteria FCC uses to determine the plan-review result. An unresolved item may be issued as a Required Correction and cause the plan set to be returned for correction.
ElectricalRequired
- #01Generator disconnect, transfer switch, and labelingLife Safety
Standby generator installation requires approved transfer switch, disconnect, and required labeling per NEC 702 / 445.
NEC 445NEC 702NEC 230.82 - #02Grounding and bondingLife Safety
Grounding electrode, equipment grounding, and bonding per NEC Article 250.
NEC 250 - #03Construction-document clarity — generator installationDocumentation
The submitted documents must clearly identify the standby generator, transfer equipment, and electrical connections so FCC can review this mandatory single-family electrical trade as part of the one residential plan review.
FBC-B 107.2.1
Section 3
Inspection Walkthrough
Inspections are listed in their typical phase order. Your own inspection list comes from your approved plans. Inspections marked “If in scope” apply only when your plans include that work. Call (772) 222-6679 with questions.
Electrical
Electrical Rough-In
If in scope- Generator pad and placementCritical
Show generator support above grade and compare placement and clearances to approved plans and manufacturer instructions.
FBC-M 304.10 - Electrical connection and transfer switchCritical
Verify transfer switch installation, wire sizing, and connection to main panel per plans
NEC 702.4NEC 445.13 - GroundingCritical
Verify generator grounding per NEC requirements
NEC 250.35
Electrical Final
Typical Final- Generator operational testCritical
Demonstrate startup and transfer behavior against approved standby-system and manufacturer commissioning instructions.
- Transfer switch operationCritical
Demonstrate startup and transfer behavior against approved standby-system and manufacturer commissioning instructions.
- Labeling and signageCritical
Verify all required labels at generator, transfer switch, and main panel
NEC 702.7NEC 445.11
