- #01Plan and document coordination
Obvious clerical, title-block, sheet-index, permit-description, or cross-sheet inconsistencies visible in the submitted documents. A Courtesy Comment on these items does not cause FCC to fail or return the plan set unless the same condition also creates a building-code compliance issue within FCC's review scope.
FBC-B 107.2.1 - #02Zoning and site coordination
Apparent setback, lot-coverage, use, or site-dimension conflicts visible in the submitted plans that could cause the plans to fail Planning and Zoning review. Planning and Zoning makes the zoning and lot-compliance determination. The absence of a Courtesy Comment is not approval of those separate requirements.
- #03Floodplain coordination
Apparent inconsistencies or missing coordination in flood-zone, design-flood-elevation, finished-floor, or flood-opening information shown on the plans that could cause the plans to fail floodplain review. The floodplain administrator makes the determination. The absence of a Courtesy Comment is not approval of those separate requirements.
- #04Fire-authority coordination
Apparent separately reviewed fire alarm, sprinkler, hood-suppression, smoke-control, or similar coordination issues visible on the plans that could cause the plans to fail fire review. The fire marshal makes the determination. The absence of a Courtesy Comment is not approval of those separate requirements.
Commercial Re-Roof
Last updated: Apr 20, 2026
Section 1
Required Documents
Submit these with your initial project package.
Always required
- Construction Plans Sealed by a Florida Registered Design ProfessionalRoofing plans sealed by a Florida-registered design professional
- Product ApprovalsFlorida Product Approvals for underlayment and roofing materials
- Roof Sheathing & Dry-In AffidavitSigned affidavit for roof sheathing and dry-in inspection compliance
Conditional
- Structural Engineer VerificationStructural engineer verification that the new roofing system does not exceed existing structural capacityWhenRequired if the new roofing system results in a weight increase of more than 10% over the existing system
Courtesy screen
Courtesy screen on every plan review
Every plan FCC reviews receives a limited courtesy screen for the items below when they are reasonably visible in the submitted documents. If we see an apparent issue that could cause the plans to fail review by another agency, we will identify it as a Courtesy Comment. Courtesy Comments alone do not cause FCC to fail or return the plan set unless the same condition also creates a building-code compliance issue within FCC's review scope. The responsible agency makes the final determination—for example, Planning and Zoning for setbacks, lot coverage, use, and other lot-compliance matters. The absence of a Courtesy Comment is not approval of those separate requirements.
Section 2
Approval criteria for this project type
These are the building-code criteria FCC uses to determine the plan-review result. An unresolved item may be issued as a Required Correction and cause the plan set to be returned for correction.
BuildingConditional review scope
- #01Attachment to existing structureLife Safety
Connection details between the new work and the existing structure must show fastener type, spacing, and embedment.
FBC-B 2002.5FBC-R R301.1 - #02Florida product approvalCode
Florida product approval (FL#) or Miami-Dade NOA must be listed for regulated products (fenestration, structural panels, covering systems).
FBC-B 1708FBC-R R301.2.1.2 - #03Plan review applicability (FBC 107.3.5)Documentation
Per FBC-B 107.3.5, plan review is not required for reroofs (Exemption #2). FCC performs this review only when the building department requires plan review or the client opts in.
FBC-B 107.3.5
Items marked Conditional review scope are non-blocking. Per FBC 107.3.5, plan review isn't required for these scopes — FCC reviews them when the building department requests it or the client wants the extra set of eyes.
Section 3
Inspection Walkthrough
Inspections are listed in their typical phase order. Your FCC inspector will confirm which apply to your project. Call (772) 222-6679 with questions.
Building
Roof Dry In, In Progress
Required- Underlayment installationCritical
Verify roof underlayment type and installation per code and manufacturer specs
FBC-R R905.1.1 - Drip edge installationCritical
Verify drip edge is installed at eaves and rakes
FBC-R R905.2.8.5 - Valley and flashingCritical
Verify valley flashing and wall flashing are properly installed
FBC-R R903.2 - Roof penetration sealing
Verify all roof penetrations are properly sealed and flashed
FBC-R R903.2 - Deck conditionCritical
Verify roof deck is in acceptable condition and any damaged sheathing has been replaced
FBC-R R803.1
Roof Final
RequiredTypical Final- Roofing material installationCritical
Verify roofing material is installed per manufacturer specs and approved plans
FBC-R R905.2 - Flashing completenessCritical
Verify all flashing is complete at walls, valleys, penetrations, and edges
FBC-R R903.2 - Ridge vent or ventilation
Verify roof ventilation is installed per plans
FBC-R R806.1 - Nailing pattern complianceCritical
Verify roofing material nailing pattern meets high-wind requirements
FBC-R R905.2 - Cleanup and debris removal
Verify job site is clean with no exposed nails or debris in gutters
FBC-B 110.3