- #01Plan and document coordination
Obvious clerical, title-block, sheet-index, permit-description, or cross-sheet inconsistencies visible in the submitted documents. A Courtesy Comment on these items does not cause FCC to fail or return the plan set unless the same condition also creates a building-code compliance issue within FCC's review scope.
FBC-B 107.2.1 - #02Zoning and site coordination
Apparent setback, lot-coverage, use, or site-dimension conflicts visible in the submitted plans that could cause the plans to fail Planning and Zoning review. Planning and Zoning makes the zoning and lot-compliance determination. The absence of a Courtesy Comment is not approval of those separate requirements.
- #03Floodplain coordination
Apparent inconsistencies or missing coordination in flood-zone, design-flood-elevation, finished-floor, or flood-opening information shown on the plans that could cause the plans to fail floodplain review. The floodplain administrator makes the determination. The absence of a Courtesy Comment is not approval of those separate requirements.
- #04Fire-authority coordination
Apparent separately reviewed fire alarm, sprinkler, hood-suppression, smoke-control, or similar coordination issues visible on the plans that could cause the plans to fail fire review. The fire marshal makes the determination. The absence of a Courtesy Comment is not approval of those separate requirements.
Commercial Remodel
Interior finish-only remodel of existing commercial space without structural or MEP changes. Use Commercial Alteration when framing or a trade system changes.
Last updated: Sep 29, 2026
Section 1
Required Documents
Submit these with your initial project package.
Always required
- Construction PlansConstruction plans reflecting the full scope of remodel work. Plans prepared by a Florida-registered architect or engineer carry that professional's seal. Plans prepared by a contractor or owner are accepted without a seal unless Florida law or the building department requires professional plans.
Conditional
- Scope of Work DescriptionVery detailed written scope of work describing all work to be performedWhenThe scope of work you type on the submission form counts. A separate document is not needed.
- Product ApprovalsFlorida Product Approvals for any regulated components being installedWhenRequired if installing new windows, doors, roofing, or other regulated products
Courtesy screen
Courtesy screen on every plan review
Every plan FCC reviews receives a limited courtesy screen for the items below when they are reasonably visible in the submitted documents. If we see an apparent issue that could cause the plans to fail review by another agency, we will identify it as a Courtesy Comment. Courtesy Comments alone do not cause FCC to fail or return the plan set unless the same condition also creates a building-code compliance issue within FCC's review scope. The responsible agency makes the final determination—for example, Planning and Zoning for setbacks, lot coverage, use, and other lot-compliance matters. The absence of a Courtesy Comment is not approval of those separate requirements.
Section 2
Approval criteria for this project type
These are the building-code criteria FCC uses to determine the plan-review result. An unresolved item may be issued as a Required Correction and cause the plan set to be returned for correction.
BuildingRequired
- #01Occupancy classificationLife Safety
Occupancy group must be clearly stated. Any change of occupancy requires FBC-EB 1001 compliance path.
FBC-B 302FBC-EB 1001 - #02Fire protection systemsLife Safety
Sprinkler coverage, alarm coverage, and emergency egress lighting required per occupancy.
FBC-B 903FBC-B 907FBC-B 1008 - #03Means of egress capacityLife Safety
Occupant load, egress width, travel distance, and number of exits must comply with FBC-B Ch. 10.
FBC-B 1004FBC-B 1005FBC-B 1006FBC-B 1017 - #04Structural alterations (commercial remodel)Life Safety
Wall removal, added openings, or roof alteration require engineered documentation per FBC-EB.
FBC-B 1603FBC-EB 503 - #05Accessibility scoping (FBC-A)Code
Alteration or new commercial work triggers accessibility requirements in altered areas and along path of travel.
FBC-A 202FBC-A 206FBC-A 202.4
Section 3
Inspection Walkthrough
Inspections are listed in their typical phase order. Your own inspection list comes from your approved plans. Inspections marked “If in scope” apply only when your plans include that work. Call (772) 222-6679 with questions.
Building
Framing
If in scope- Wall stud spacing and sizeCritical
Verify stud size and spacing match approved plans
- Headers and beamsCritical
Verify header and beam sizes over openings per plans
- Top and bottom plate connectionsCritical
Verify double top plates with proper lapping and anchored bottom plates
- Corner and intersection bracingCritical
Verify proper bracing at corners and wall intersections
- Window and door rough openingsCritical
Verify rough openings match approved plans for size and location
- Hurricane straps and hold-downsCritical
Verify hurricane straps and hold-down hardware installed per plans
- Fire blocking
Verify fire blocking is installed at required locations
Roof Dry-In
If in scope- Underlayment installationCritical
Verify roof underlayment is installed per code and manufacturer specs
- Underlayment typeCritical
Match installed underlayment to the approved roof system and manufacturer instructions.
- Lap and fasteningCritical
Show laps, seams, and fasteners before the roof covering conceals them.
- Dry-in continuityCritical
Show continuous dry-in at edges, transitions, and penetrations.
- Wall dry-in where requiredCritical
Where the approved scope includes wall dry-in, show the barrier and flashing before covering.
FBC-B 110.3
Plumbing
Plumbing Rough-In
If in scope- Supply pipe sizing and materialCritical
Verify supply pipe sizes and material match approved plans
FBC-P 604.3FBC-P 605.4 - DWV pipe sizing and slopeCritical
Verify drain, waste, and vent pipe sizes and slope per plans
FBC-P 704.1 - Pipe support and hangingCritical
Verify pipes are properly supported at required intervals
FBC-P 308.1 - Vent termination locations
Show vent routing and approved termination through the roof or side wall before concealment.
FBC-P 903.1 - Water heater rough-in
Where a water heater is in scope, compare rough location and connections with approved plans and manufacturer instructions. Show a pan when tank leakage could cause damage.
FBC-P 502.1FBC-P 504.7 - Required rough testsCritical
Have the required water, drain, and vent tests ready before walls close.
FBC-P 312.1 - Shower and tub workCritical
Where shower or tub work is in scope, show pan/liner or tub installation and the required test before concealment.
Electrical
Electrical Rough-In
If in scope- Panel installationCritical
Verify electrical panel is properly mounted and sized per plans
- Wire sizing per circuitsCritical
Verify wire gauge matches breaker amperage for each circuit
NEC 240.4 - Box fill and installationCritical
Verify electrical boxes are properly installed and not overfilled
NEC 314.16 - Grounding and bondingCritical
Verify grounding electrode system and bonding connections
NEC 250.50 - GFCI and AFCI locationsCritical
Verify GFCI and AFCI protection is provided where required
NEC 210.8NEC 210.12 - Smoke and CO alarm installation methodsCritical
For applicable dwellings, show smoke alarm power and permitted wired or listed wireless interconnection. CO alarms may be hard-wired or battery powered. Match approved scope.
FBC-R R314.4FBC-R R314.6FBC-R R315.1.1 - Concealed wiring visibleCritical
Keep boxes, cable routes, and connections exposed until rough inspection.
Mechanical
Mechanical Rough-In
If in scope- Ductwork installationCritical
Verify duct sizes, routing, and support match approved plans
FBC-M 603.1 - Duct sealingCritical
Verify duct joints and connections are properly sealed
FBC-M 603.9 - Refrigerant line installation
Where refrigerant lines are in scope, keep joints exposed before covering (FBC-M 1107.7). Compare sizing and insulation with approved plans and equipment instructions.
FBC-M 1107.7 - Equipment placementCritical
Verify air handler and condenser locations per plans with required clearances
FBC-M 304.1 - Return air pathway
Verify return air pathways are properly sized and located
FBC-M 601.6 - Concealed mechanical work visibleCritical
Leave duct, line, and exhaust routes accessible before walls close.
Building
Insulation
If in scope- Wall cavity insulation R-valueCritical
Verify wall insulation R-value matches energy calculations
FBC-E C402.2 - Ceiling/attic insulation R-valueCritical
Verify ceiling or attic insulation R-value per energy calculations
FBC-E C402.2 - Insulation coverage and gapsCritical
Verify no gaps, voids, or compression in insulation installation
FBC-E C402.2 - Air sealing
Verify air sealing at penetrations, top plates, and rim joists
FBC-E C402.5
Roof In-Progress
If in scope- Drip edge installationCritical
Verify drip edge is installed at eaves and rakes
- Valley and flashingCritical
Verify valley flashing and wall flashing are properly installed
- Roof penetration sealing
Verify all roof penetrations are properly sealed and flashed
- Covering materialCritical
Match roof tile, shingles, or metal panels to the approved plans and product approval.
- Covering attachmentCritical
Show fastener or clip pattern before it is concealed by the next course.
- Flashing installationCritical
Show flashing at valleys, walls, edges, and penetrations while accessible.
FBC-R R903.2 - Roof transitionsCritical
Check ridges, hips, terminations, and transitions against approved details.
- Roof insulationCritical
Where specified, show insulation thickness and attachment before covering.
Exterior Wall Covering (Lath / Stucco / Siding)
If in scope- Wall covering material and installationCritical
Verify exterior wall covering material matches approved plans and is properly installed
- Weather-resistive barrierCritical
Verify weather-resistive barrier is properly installed behind cladding
- Flashing at penetrations and transitionsCritical
Verify flashing is installed at windows, doors, and wall transitions
- Fastener pattern and spacing
Verify cladding fastener type and spacing per manufacturer and plans
- Lath and accessoriesCritical
For stucco work, show lath attachment and accessories before cement finish.
- Siding or veneer attachmentCritical
Show fastening and support of installed siding or veneer.
Drywall / Gypsum Board
If in scopeBD-DependentMost jurisdictions skip this inspection for this project type. Confirm with your building department whether they'll require it.
- Drywall thickness and typeCritical
Match board type, thickness, exposure rating, and layers to the approved rated or shear assembly.
- Fastener spacingCritical
Verify screw or nail spacing meets code requirements
- Fire-rated assembliesCritical
Verify fire-rated walls and ceilings have proper drywall layers per rating
Electrical
Electrical Final
If in scope- Panel complete and labeledCritical
Verify panel cover installed, all breakers labeled, no open knockouts
NEC 408.4NEC 408.7 - GFCI and AFCI operationalCritical
Verify all GFCI and AFCI devices test and reset properly
NEC 210.8NEC 210.12 - Receptacle and switch functionCritical
Verify outlets and switches operate correctly throughout
- Light fixtures installed
Where the approved scope requires lighting outlets, show the installed luminaires or approved alternatives and demonstrate operation.
NEC 210.70 - Exterior lighting and outletsCritical
Where in scope, demonstrate outdoor GFCI protection and exterior entrance lighting.
NEC 210.8NEC 210.70 - Equipment energized safelyCritical
Demonstrate installed equipment and controls operate as intended.
Plumbing
Plumbing Final
If in scope- Fixture setting, connections and operationCritical
Show in-scope fixtures level and aligned, connected to required water and drainage systems, and operating without visible leaks.
FBC-P 405.3FBC-P 301.3FBC-P 301.4 - No visible leaksCritical
During the live fixture run, show exposed connections and surrounding areas with no visible leaks.
- Water heater installationCritical
Where a water heater is in scope, show the installed heater, relief valve and discharge piping; show a pan and drain where leakage could cause damage.
FBC-P 504.4FBC-P 504.6FBC-P 504.7 - Hose bibbs and exterior plumbing
Verify exterior hose bibbs have backflow prevention
FBC-P 608.16.4.2 - All fixtures connectedCritical
Confirm fixtures and water-using equipment are installed and connected.
Mechanical
Mechanical Final
If in scope- Installed mechanical system operationCritical
Demonstrate each mechanical system in the approved scope. Show heating and cooling modes only if the installed equipment provides them.
- Equipment labels and data plates
Verify equipment nameplates match approved plans for capacity and efficiency
FBC-M 304.1 - Installed mechanical equipmentCritical
Show equipment installed for this scope, with access and clearances against approved plans and manufacturer instructions.
FBC-M 304.1 - Condensate drainCritical
Where cooling equipment produces condensate, show the drain and approved termination.
FBC-M 307.2 - Duct registers and grilles
Where ducted supply or return air is in scope, show representative installed registers and grilles.
FBC-M 603.18 - Equipment operationCritical
Demonstrate system operation in heating, cooling, or exhaust mode as applicable.
Building
Building Final
Typical Final- Egress doors and hardwareCritical
Verify egress doors provide minimum 32-inch clear width and proper hardware
- Smoke alarms installed and operationalCritical
Where the approved occupancy includes dwelling or sleeping units, show required smoke alarms and demonstrate operation.
- CO alarms installedCritical
Where the approved occupancy and equipment trigger carbon monoxide alarms, show installed and operating devices.
- Emergency escape openingsCritical
Where approved sleeping rooms require emergency escape openings, show representative opening dimensions and operation.
- Stairway complianceCritical
If stairs are in scope, demonstrate approved rise, run, handrails, and accessible route.
- Address numbers visible
Verify address numbers are posted and visible from street
- Exterior finishes complete
Verify exterior cladding, trim, and weatherproofing are complete
- Site grading and drainage
Show finished grading and drainage against approved site plans; no universal residential 6-in-10-ft rule.