- #01Plan and document coordination
Obvious clerical, title-block, sheet-index, permit-description, or cross-sheet inconsistencies visible in the submitted documents. A Courtesy Comment on these items does not cause FCC to fail or return the plan set unless the same condition also creates a building-code compliance issue within FCC's review scope.
FBC-B 107.2.1 - #02Zoning and site coordination
Apparent setback, lot-coverage, use, or site-dimension conflicts visible in the submitted plans that could cause the plans to fail Planning and Zoning review. Planning and Zoning makes the zoning and lot-compliance determination. The absence of a Courtesy Comment is not approval of those separate requirements.
- #03Floodplain coordination
Apparent inconsistencies or missing coordination in flood-zone, design-flood-elevation, finished-floor, or flood-opening information shown on the plans that could cause the plans to fail floodplain review. The floodplain administrator makes the determination. The absence of a Courtesy Comment is not approval of those separate requirements.
- #04Fire-authority coordination
Apparent separately reviewed fire alarm, sprinkler, hood-suppression, smoke-control, or similar coordination issues visible on the plans that could cause the plans to fail fire review. The fire marshal makes the determination. The absence of a Courtesy Comment is not approval of those separate requirements.
Multi Family Alteration
Structural or layout alteration of an existing apartment or condo building; include MEP inspections only for trades on approved plans.
Last updated: Sep 29, 2026
Section 1
Required Documents
Submit these with your initial project package.
Always required
- Scope of Work DescriptionVery detailed written scope of work describing all work to be performed
- Construction PlansConstruction plans reflecting the full scope of alteration work. Plans prepared by a Florida-registered architect or engineer carry that professional's seal. Plans prepared by a contractor or owner are accepted without a seal unless Florida law or the building department requires professional plans.
Conditional
- Product ApprovalsFlorida Product Approvals for any regulated components being installedWhenRequired if installing new windows, doors, roofing, or other regulated products
Courtesy screen
Courtesy screen on every plan review
Every plan FCC reviews receives a limited courtesy screen for the items below when they are reasonably visible in the submitted documents. If we see an apparent issue that could cause the plans to fail review by another agency, we will identify it as a Courtesy Comment. Courtesy Comments alone do not cause FCC to fail or return the plan set unless the same condition also creates a building-code compliance issue within FCC's review scope. The responsible agency makes the final determination—for example, Planning and Zoning for setbacks, lot coverage, use, and other lot-compliance matters. The absence of a Courtesy Comment is not approval of those separate requirements.
Section 2
Approval criteria for this project type
These are the building-code criteria FCC uses to determine the plan-review result. An unresolved item may be issued as a Required Correction and cause the plan set to be returned for correction.
BuildingRequired
- #01Fire-rated unit separationLife Safety
Dwelling-unit and corridor separations must maintain the original fire-resistance rating through any new work.
FBC-B 420FBC-B 711FBC-B 708 - #02Means of egress in altered areasLife Safety
Alterations must not reduce the capacity, width, or arrangement of existing means of egress.
FBC-B 1004FBC-B 1005 - #03Structural alterations (MF)Life Safety
Wall removal or beam substitution requires engineered detail.
FBC-B 1603FBC-EB 503 - #04Sound transmission (altered party walls)Performance
Altered inter-unit assemblies must meet FBC-B 1207 STC/IIC minimums.
FBC-B 1207
MechanicalConditional review scope
- #01HVAC equipment changeoutPerformance
If HVAC changeout or new system is in scope, verify equipment schedule with capacity matches scope.
FBC-E R403
ElectricalConditional review scope
- #01AFCI/GFCI upgrade in work areaLife Safety
If scope includes electrical work in kitchens, bathrooms, bedrooms, or wet locations, verify AFCI/GFCI coverage.
NEC 210.8NEC 210.12
PlumbingConditional review scope
- #01Fixture additions in remodel scopeDocumentation
If scope adds or relocates plumbing fixtures (kitchen, bathroom remodel), verify basic fixture layout and water heater adequacy are noted.
FBC-P 701FBC-P 901
Items marked Conditional review scope are non-blocking. Per FBC 107.3.5, plan review isn't required for these scopes — FCC reviews them when the building department requests it or the client wants the extra set of eyes.
Section 3
Inspection Walkthrough
Inspections are listed in their typical phase order. Your own inspection list comes from your approved plans. Inspections marked “If in scope” apply only when your plans include that work. Call (772) 222-6679 with questions.
Building
Framing
If in scope- Wall stud spacing and sizeCritical
Verify stud size and spacing match approved plans
- Headers and beamsCritical
Verify header and beam sizes over openings per plans
- Top and bottom plate connectionsCritical
Verify double top plates with proper lapping and anchored bottom plates
- Corner and intersection bracingCritical
Verify proper bracing at corners and wall intersections
- Window and door rough openingsCritical
Verify rough openings match approved plans for size and location
- Hurricane straps and hold-downsCritical
Verify hurricane straps and hold-down hardware installed per plans
- Fire blocking
Verify fire blocking is installed at required locations
Roof Dry-In
If in scope- Underlayment installationCritical
Verify roof underlayment is installed per code and manufacturer specs
Plumbing
Plumbing Rough-In
If in scope- Supply pipe sizing and materialCritical
Verify supply pipe sizes and material match approved plans
FBC-P 604.3FBC-P 605.4 - DWV pipe sizing and slopeCritical
Verify drain, waste, and vent pipe sizes and slope per plans
FBC-P 704.1 - Pipe support and hangingCritical
Verify pipes are properly supported at required intervals
FBC-P 308.1 - Vent termination locations
Verify vent route and planned termination through the roof or side wall as approved.
FBC-P 903.1 - Water heater rough-in
Where a water heater is in scope, compare rough location and connections with approved plans and manufacturer instructions; show a pan if leakage could cause damage.
FBC-P 502.1FBC-P 504.7
Electrical
Electrical Rough-In
If in scope- Panel installationCritical
Verify electrical panel is properly mounted and sized per plans
- Wire sizing per circuitsCritical
Verify wire gauge matches breaker amperage for each circuit
NEC 240.4 - Box fill and installationCritical
Verify electrical boxes are properly installed and not overfilled
NEC 314.16 - GFCI and AFCI locationsCritical
Verify GFCI and AFCI protection is provided where required
NEC 210.8NEC 210.12 - Alarm installation methods where applicableCritical
Where the approved occupancy and scope require alarms, show the specified smoke-alarm power/interconnection method and any CO alarm installation; do not assume both are hardwired.
FBC-B 907.2.11 - Grounding and bondingCritical
Verify grounding electrode system and bonding connections
NEC 250.50
Mechanical
Mechanical Rough-In
If in scope- Ductwork installationCritical
Verify duct sizes, routing, and support match approved plans
FBC-M 603.1 - Duct sealingCritical
Verify duct joints and connections are properly sealed
FBC-M 603.9 - Equipment placementCritical
Verify air handler and condenser locations per plans with required clearances
FBC-M 304.1 - Refrigerant line installation
Match refrigerant line size, insulation, and route to approved plans; leave field-installed joints visible before cover.
FBC-M 1107.7 - Return air pathway
Show return-air path and grille or transfer opening against approved mechanical plans.
FBC-M 601.6
Building
Insulation
If in scope- Wall cavity insulation R-valueCritical
Match insulation to the approved energy compliance path and plans; confirm whether this building uses the residential or commercial energy provisions.
FBC-E R402.1.2FBC-E C402.2 - Ceiling/attic insulation R-valueCritical
Match insulation to the approved energy compliance path and plans; confirm whether this building uses the residential or commercial energy provisions.
FBC-E R402.1.2FBC-E C402.2 - Insulation coverage and gapsCritical
Verify no gaps, voids, or compression in insulation installation
FBC-E R402.4.1.1FBC-E C402.2 - Air sealing
Verify air sealing at penetrations, top plates, and rim joists
FBC-E R402.4.1.1FBC-E C402.5
Roof In-Progress
If in scope- Drip edge installationCritical
Verify drip edge is installed at eaves and rakes
- Valley and flashingCritical
Verify valley flashing and wall flashing are properly installed
- Roof penetration sealing
Verify all roof penetrations are properly sealed and flashed
- Covering materialCritical
Match roof tile, shingles, or metal panels to the approved plans and product approval.
- Covering attachmentCritical
Show fastener or clip pattern before it is concealed by the next course.
- Flashing installationCritical
Show flashing at valleys, walls, edges, and penetrations while accessible.
Exterior Wall Covering (Lath / Stucco / Siding)
If in scope- Wall covering material and installationCritical
Verify exterior wall covering material matches approved plans and is properly installed
- Weather-resistive barrierCritical
Verify weather-resistive barrier is properly installed behind cladding
- Flashing at penetrations and transitionsCritical
Verify flashing is installed at windows, doors, and wall transitions
- Fastener pattern and spacing
Verify cladding fastener type and spacing per manufacturer and plans
Drywall / Gypsum Board
If in scopeBD-DependentMost jurisdictions skip this inspection for this project type. Confirm with your building department whether they'll require it.
- Drywall thickness and typeCritical
Match board type, thickness, exposure rating, and layers to the approved rated or shear assembly.
- Fastener spacingCritical
Verify screw or nail spacing meets code requirements
- Fire-rated assembliesCritical
Verify fire-rated walls and ceilings have proper drywall layers per rating
Electrical
Electrical Final
If in scope- Panel complete and labeledCritical
Verify panel cover installed, all breakers labeled, no open knockouts
NEC 408.4NEC 408.7 - GFCI and AFCI operationalCritical
Verify all GFCI and AFCI devices test and reset properly
NEC 210.8NEC 210.12 - Receptacle and switch functionCritical
Verify outlets and switches operate correctly throughout
- Light fixtures installed
Verify all light fixtures are installed and operational
NEC 210.70 - Exterior lighting and outletsCritical
Where in scope, demonstrate outdoor GFCI protection and required exterior entrance lighting.
NEC 210.8NEC 210.70
Plumbing
Plumbing Final
If in scope- Fixture installation and operationCritical
For fixtures in the approved scope, show level alignment, water and drainage connections, and live operation.
FBC-P 405.3FBC-P 301.3FBC-P 301.4 - Water heater installationCritical
Where a water heater is in scope, show the installed relief valve and discharge piping. For a storage-type heater, show a pan only where tank leakage would cause damage. Show the pan drain where required; a replacement needs no new pan drain if none was previously installed (FBC-P 504.7.2).
FBC-P 504.4FBC-P 504.6FBC-P 504.7FBC-P 504.7.1FBC-P 504.7.2 - No visible leaksCritical
During the live fixture run, show exposed connections and surrounding areas with no visible leaks.
- Hose bibbs and exterior plumbing
Where exterior hose connections are in scope, show backflow protection and operation.
FBC-P 608.16.4.2
Mechanical
Mechanical Final
If in scope- System operational testCritical
Demonstrate the installed system operating in its approved heating, cooling, exhaust, or hood mode as applicable.
- Air handler and condenser installationCritical
If an air handler or condenser is in scope, show installed equipment, clearance, support, and manufacturer labels.
FBC-M 304.1 - Condensate drainCritical
Where cooling equipment produces condensate, show the drain and approved termination.
FBC-M 307.2 - Duct registers and grilles
Show supply and return openings and demonstrate airflow at representative locations.
FBC-M 603.18 - Equipment labels and data plates
Match installed equipment model and rating to approved plans and manufacturer instructions.
FBC-M 304.1
Building
Building Final
Typical Final- Egress doors and hardwareCritical
Verify egress doors provide minimum 32-inch clear width and proper hardware
- Smoke alarms installed and operationalCritical
Show required smoke alarms in affected dwelling units and demonstrate operation.
- CO alarms installedCritical
Verify carbon monoxide alarms where required
- Emergency escape openingsCritical
Verify bedroom windows meet egress size requirements
- Stairway complianceCritical
Verify stair rise, run, handrail height, and landing dimensions
- Address numbers visible
Verify address numbers are posted and visible from street
- Exterior finishes complete
Verify exterior cladding, trim, and weatherproofing are complete
- Site grading and drainage
Show finished grading and drainage against approved site plans; no universal 6-in-10-ft rule.