- #01Plan and document coordination
Obvious clerical, title-block, sheet-index, permit-description, or cross-sheet inconsistencies visible in the submitted documents. A Courtesy Comment on these items does not cause FCC to fail or return the plan set unless the same condition also creates a building-code compliance issue within FCC's review scope.
FBC-B 107.2.1 - #02Zoning and site coordination
Apparent setback, lot-coverage, use, or site-dimension conflicts visible in the submitted plans that could cause the plans to fail Planning and Zoning review. Planning and Zoning makes the zoning and lot-compliance determination. The absence of a Courtesy Comment is not approval of those separate requirements.
- #03Floodplain coordination
Apparent inconsistencies or missing coordination in flood-zone, design-flood-elevation, finished-floor, or flood-opening information shown on the plans that could cause the plans to fail floodplain review. The floodplain administrator makes the determination. The absence of a Courtesy Comment is not approval of those separate requirements.
- #04Fire-authority coordination
Apparent separately reviewed fire alarm, sprinkler, hood-suppression, smoke-control, or similar coordination issues visible on the plans that could cause the plans to fail fire review. The fire marshal makes the determination. The absence of a Courtesy Comment is not approval of those separate requirements.
Single Family Hot Water Heater Changeout
Replacement of existing water heater with like-for-like or upgraded unit
Last updated: Apr 21, 2026
Section 1
Required Documents
Submit these with your initial project package.
Always required
- Equipment SpecificationsManufacturer specifications for the replacement water heater including capacity, fuel type, and input rating
- AHRI Certification SheetAHRI performance certification showing Uniform Energy Factor (UEF) rating for the replacement water heater
Courtesy screen
Courtesy screen on every plan review
Every plan FCC reviews receives a limited courtesy screen for the items below when they are reasonably visible in the submitted documents. If we see an apparent issue that could cause the plans to fail review by another agency, we will identify it as a Courtesy Comment. Courtesy Comments alone do not cause FCC to fail or return the plan set unless the same condition also creates a building-code compliance issue within FCC's review scope. The responsible agency makes the final determination—for example, Planning and Zoning for setbacks, lot coverage, use, and other lot-compliance matters. The absence of a Courtesy Comment is not approval of those separate requirements.
Section 2
Approval criteria for this project type
These are the building-code criteria FCC uses to determine the plan-review result. An unresolved item may be issued as a Required Correction and cause the plan set to be returned for correction.
PlumbingRequired
- #01Water heater installation requirementsCode
Replacement water heater installation must include T&P valve, expansion control, drain pan, and proper combustion air / venting for fuel-fired units.
FBC-P 504FBC-M 303FBC-FG - #02Construction-document clarity — water heater changeoutDocumentation
The submitted documents must clearly identify the water heater replacement, location, and plumbing connections so FCC can review this mandatory single-family plumbing trade as part of the one residential plan review.
FBC-B 107.2.1
Section 3
Inspection Walkthrough
Inspections are listed in their typical phase order. Your FCC inspector will confirm which apply to your project. Call (772) 222-6679 with questions.
Plumbing
Rough Plumbing
Required- Water heater specificationsCritical
Verify new water heater model, capacity, and energy rating match approved plans
FBC-P 607.1 - TPR valve and discharge pipeCritical
Verify temperature and pressure relief valve is installed with proper discharge pipe to approved termination
FBC-P 607.5 - Drain pan and drain lineCritical
Verify drain pan is installed under unit with drain line routed to approved location
FBC-P 607.4 - Supply connectionsCritical
Verify hot and cold water connections are properly made with no leaks
FBC-P 607.1
Final Plumbing
RequiredTypical Final- Operational testCritical
Verify water heater heats water and all fixtures receive hot water
FBC-P 607.1 - No visible leaksCritical
Verify no leaks at any connection point
FBC-P 312.1 - Seismic strapping (if required)
Verify strapping is installed where required
FBC-P 607.1