- #01Plan and document coordination
Obvious clerical, title-block, sheet-index, permit-description, or cross-sheet inconsistencies visible in the submitted documents. A Courtesy Comment on these items does not cause FCC to fail or return the plan set unless the same condition also creates a building-code compliance issue within FCC's review scope.
FBC-B 107.2.1 - #02Zoning and site coordination
Apparent setback, lot-coverage, use, or site-dimension conflicts visible in the submitted plans that could cause the plans to fail Planning and Zoning review. Planning and Zoning makes the zoning and lot-compliance determination. The absence of a Courtesy Comment is not approval of those separate requirements.
- #03Setbacks from property lines and structures
Pool setbacks from property lines, septic fields and easements are set by local zoning, which the jurisdiction reviews. Note visible conflicts as a courtesy observation.
Local zoning ordinance - #04Floodplain coordination
Apparent inconsistencies or missing coordination in flood-zone, design-flood-elevation, finished-floor, or flood-opening information shown on the plans that could cause the plans to fail floodplain review. The floodplain administrator makes the determination. The absence of a Courtesy Comment is not approval of those separate requirements.
- #05Fire-authority coordination
Apparent separately reviewed fire alarm, sprinkler, hood-suppression, smoke-control, or similar coordination issues visible on the plans that could cause the plans to fail fire review. The fire marshal makes the determination. The absence of a Courtesy Comment is not approval of those separate requirements.
Single Family Pool Construction
Build a new residential pool or spa, including shell steel and bonding, piping, electrical work, and the final barrier and safety check.
Last updated: Sep 29, 2026
Section 1
Required Documents
Submit these with your initial project package.
Always required
- Construction PlansPool construction plans showing layout, dimensions, structural details, plumbing, and electrical. Plans prepared by a Florida-registered architect or engineer carry that professional's seal. Plans prepared by a contractor or owner are accepted without a seal unless Florida law or the building department requires professional plans.
Conditional
- TDH CalculationsTotal dynamic head (TDH) calculation or pump sizing for the pool circulation system.WhenA TDH value, hydraulic table, or pump curve on the pool engineering plans counts. A separate calculation sheet is not needed to start review.
- Equipment SpecificationsManufacturer specifications for pump, filter, heater, and other pool equipment (recommended, not required)WhenGuidance only: Not required. FCC recommends manufacturer cut sheets (pump, filter, heater, lights, drain covers) because some building departments ask for them. An engineer's equipment table on the plans is enough, and missing cut sheets are never a reason to reject the submission.
- Site Plan / SurveySite plan or survey showing pool location, setbacks, and safety barrier locationsWhenUsually a sheet in the pool plans, or a survey with the pool drawn on it. Not needed to start review.
- Safety Barrier AffidavitOptional contractor statement of how the pool will be protected: a barrier or safety cover, plus door alarms, self-closing doors, or a pool alarm where the house is part of the barrier.WhenGuidance only: Not required, and never a reason to reject a submission, even when the plans do not show the pool barrier or safety features. If your plans do not show how the pool will be protected, you may attach FCC's optional form from freedomcodecompliance.com/forms.
Courtesy screen
Courtesy screen on every plan review
Every plan FCC reviews receives a limited courtesy screen for the items below when they are reasonably visible in the submitted documents. If we see an apparent issue that could cause the plans to fail review by another agency, we will identify it as a Courtesy Comment. Courtesy Comments alone do not cause FCC to fail or return the plan set unless the same condition also creates a building-code compliance issue within FCC's review scope. The responsible agency makes the final determination—for example, Planning and Zoning for setbacks, lot coverage, use, and other lot-compliance matters. The absence of a Courtesy Comment is not approval of those separate requirements.
Section 2
Approval criteria for this project type
These are the building-code criteria FCC uses to determine the plan-review result. An unresolved item may be issued as a Required Correction and cause the plan set to be returned for correction.
BuildingRequired
- #01Pool barrier complianceLife Safety
Verify a code-compliant pool barrier is shown on plans - height, clearances, gate self-closing/self-latching hardware, and door alarms on dwelling openings facing pool.
FBC-R R4501.17Florida Statutes 515.27 - #02Pool shell structural designLife Safety
Verify pool shell engineering is provided with soil bearing, reinforcement, and shell thickness.
FBC-R R4501.6.1ACI 318 - #03Deck and coping designCode
Verify pool deck slopes, slip resistance, and coping connection are noted.
FBC-R R4501.6.1FBC-R R326 - #04Engineer seal on structural, when engineeredDocumentation
When a Florida engineer prepared the pool structural drawings, confirm the document carries a current Florida engineer seal.
Florida Statutes Chapter 471
MechanicalConditional review scope
- #01Pool heater clearances (if gas)Life Safety
If a gas pool heater is specified, verify combustion air and venting clearances are shown.
FBC-FG 617.1FBC-FG 304.1
ElectricalRequired
- #01Equipotential bonding gridLife Safety
Verify a complete equipotential bonding grid is shown - pool shell reinforcement, metallic components within 5 feet, pool equipment, and perimeter bonding around the pool.
NEC 680.26 - #02GFCI protection for pool circuitsLife Safety
Verify GFCI protection is shown for pool equipment circuits, receptacles, and underwater luminaires.
NEC 680.5NEC 680.22NEC 680.23 - #03Underwater luminairesLife Safety
If underwater pool lights are included, verify they comply with NEC 680.23 (low-voltage preferred; line voltage requires specific installation).
NEC 680.23 - #04Equipment disconnect locationCode
Verify a disconnecting means is shown within sight of pool equipment, at least 5 feet horizontally from the inside wall of the pool.
NEC 680.13 - #05Underground wiring methodsCode
Verify burial depth and wiring method for underground pool circuits.
NEC 300.5NEC 680.11
PlumbingRequired
- #01Suction entrapment prevention (VGBA)Life Safety
Verify suction outlets comply with Virginia Graeme Baker Act requirements - dual main drains or unblockable single drain, ANSI/APSP-16 compliant covers.
FBC-R R4501.6.615 USC 8003 (VGBA) - #02Filtration and circulationCode
Verify filtration equipment is sized for pool volume and turnover rate is specified.
FBC-R R4501.20 - #03Backflow prevention on auto-fillCode
If an auto-fill or auto-leveler is included, verify a backflow prevention device is specified on the water supply.
FBC-P 608FBC-R R4501.9
Items marked Conditional review scope are non-blocking. Per FBC 107.3.5, plan review isn't required for these scopes — FCC reviews them when the building department requests it or the client wants the extra set of eyes.
Section 3
Inspection Walkthrough
Inspections are listed in their typical phase order. Your own inspection list comes from your approved plans. Inspections marked “If in scope” apply only when your plans include that work. Call (772) 222-6679 with questions.
Plumbing
Plumbing Underground
- Pipe installation and supportCritical
Verify plumbing lines are properly installed and supported per plans
FBC-B 110.3 - Burial depthCritical
Measure pipe cover against approved plans and utility requirements before backfill.
FBC-B 110.3 - Pressure testCritical
Verify plumbing system holds required pressure test
FBC-P 312.2 - Pipe sizing per plans
Verify pipe sizes match approved plans
FBC-P 604.1
Electrical
Electrical Underground
- Conduit and wiring installationCritical
Verify electrical conduit and wiring are properly installed per plans
NEC 680.11 - Burial depth verificationCritical
Verify conduit burial depth meets minimum code requirements
NEC 680.11 - Pool-area underground wiring methodCritical
Check wiring method and routing near or under the pool against approved plans and NEC 680.11; do not impose a blanket five-foot setback.
NEC 680.11 - Bonding connections at undergroundCritical
Show pool equipotential-bonding parts that will be buried; verify other underground equipment grounding separately.
NEC 680.26NEC 680.6 - Equipment grounding at underground boxesCritical
Where conductors splice or terminate in an underground box, show equipment-grounding conductor continuity and connections before backfill.
NEC 250.148
Building
Footing / Grade Beam
If in scope- Separate structural footing onlyCritical
Use this inspection only if the approved pool plans include a separate structural footing or grade beam.
- Footing forms and steelCritical
If applicable, show the footing location, forms, dimensions, and reinforcing before the pour.
- Plan matchCritical
Confirm the separate footing matches the approved structural detail.
Pool Steel / Bonding
- Excavation, shell steel, and main drainCritical
Show excavation, steel, bonding, and main drain before concrete or gunite.
FBC-B 110.3 - Equipotential bondingCritical
Trace shell and perimeter bonding to metallic parts before burial.
NEC 680.26
Plumbing
Plumbing Rough-In
- Equipment pad plumbing connectionsCritical
Verify plumbing connections at pump, filter, and heater locations
FBC-B 110.3 - Suction outlet complianceCritical
Verify suction outlets meet entrapment avoidance requirements
ISPSC 307.1
Electrical
Electrical Rough-In
- Equipment wiringCritical
Verify electrical wiring to pump, filter, heater per plans
NEC 680.21 - GFCI protectionCritical
Show required GFCI protection for pool motor and pool-area receptacles as applicable.
NEC 680.21NEC 680.22 - Receptacle locations and distancesCritical
Verify receptacle placement meets minimum distance requirements from pool
NEC 680.22 - Equipment bondingCritical
Show equipotential bonds for pool equipment and other parts identified by the approved bonding plan.
NEC 680.26
Building
Pool Deck
If in scope- Deck reinforcement layoutCritical
Verify deck rebar spacing, overlap, and placement per plans
- Approved perimeter bonding methodCritical
Verify the approved conductive perimeter/deck bonding method and connections before the pour; a separate wire is not universal.
NEC 680.26 - Plumbing and electrical conduit in place
Verify plumbing lines and electrical conduit are installed prior to pour
- Deck drainageCritical
Measure deck slope and show drainage away from the pool or toward approved deck drains.
ISPSC 306.5ISPSC 306.5.1
Electrical
Electrical Final
- Pool light installationCritical
Verify pool lights are properly installed per plans and NEC
NEC 680.23 - Equipotential bonding completeCritical
Compare required metallic parts and connections with the approved pool bonding plan; do not impose a blanket five-foot rule.
NEC 680.26 - GFCI protection operationalCritical
Demonstrate required GFCI devices for pool motor and pool-area receptacles operate.
NEC 680.21NEC 680.22 - Grounding connectionsCritical
Verify pool electrical equipment grounding separately from equipotential bonding.
NEC 680.6 - Disconnect switchCritical
Show the approved disconnecting means and accessible location against the equipment plans.
FBC-B 110.3
Plumbing
Plumbing Final
- Pump and filter operationCritical
Demonstrate pump and filter operation against the approved equipment schedule and manufacturer instructions.
- Drain covers and suction safetyCritical
Show listed suction outlet fitting assemblies and approved entrapment-avoidance design.
ISPSC 311.1ISPSC 312.4.4 - Skimmer installationCritical
Compare installed skimmers with approved pool design and manufacturer instructions.
ISPSC 316.1 - Heater installationCritical
If a heater is in scope, compare the installed heater and plumbing with the approved equipment plan and manufacturer instructions.
- Backflow preventionCritical
Show required backflow protection on the affected potable-water outlet.
FBC-P 608.16
Building
Pool Final (incl. barrier)
Typical Final- Completed poolCritical
Show the finished pool and equipment against approved plans.
FBC-B 110.3 - Barrier and gatesCritical
Demonstrate barrier continuity and gates self-closing and self-latching.
FBC-B 454.2.17ISPSC 305.3 - Safety devicesCritical
Demonstrate approved alarms or other required safety devices.
FBC-B 454.2.17 - Suction outletsCritical
Show installed covers and suction system identification.
ISPSC 311.1ISPSC 312.4.4 - Final plan matchCritical
Compare finished pool, deck, barrier, and access with the approved plan.
FBC-B 110.3